SHSL series - type ultrasonic material (liquid) level meter
Functional features:
L advanced ECHODISCOVERY echo processing technology can be applied in various complex working conditions.
L "false echo learning" can correctly confirm the true echo and obtain accurate measurement results.
The temperature sensor is built into the transducer to realize the temperature compensation of the measured value.
L signal processing and power supply system separation, the use of advanced digital processing technology, strong anti-interference ability, high precision.
L ultrasonic transducer adopts the foreign patent technology of the best acoustic matching to improve the signal strength and realize the accurate measurement.
Application:
It is suitable for chemical container level measurement, pond/river level measurement, water treatment plant level measurement, lime storage warehouse level measurement, barn, solid and liquid seasoning storage tank level measurement, boiler water tank level measurement, grinding equipment inlet level measurement.
Technical parameters:
Type no. : SHSL22
Working mode: acoustic measurement
Application: all kinds of industrial field level, liquid level measurement
Measurement range :(0.25-4) m
Operating frequency: 40KHz 2KHz
Measurement accuracy: 0.5% resolution: 1mm
Display resolution: 1mm
Process temperature (40 ~ 70 ℃)
Process pressure :(0.02-0.1)MPa
Signal output :(4 ~ 20) mA/HART
Power source: two-wire system (DC24V)
Four-wire system (DC24V/AC220V)
Power consumption: Max. 22.5 mA /
Max. 1 va 1 w
Transducer material: PTFE/ABS/PC
Transducer structure: totally enclosed horn
Field display: optional
Blind area: 0.35 m
Load resistance: Max. 500 Ω
Weight: 2 kg
Protection level: IP66/IP67
Outer shell: aluminum alloy/stainless steel 316L/PTFE/ anti-static PP
Process connection: thread g11/2a/thread 11/2npt/flange
Flange selection :(PTFE/PP) flange/stainless steel flange
SHRD21 pulse radar object (liquid) level meter
Features: small beam Angle, high and concentrated energy, strong anti-interference ability, accurate and reliable measurement;
Small antenna size, easy to install and install dust cover and other antenna protection devices.
Pulse working mode, very low transmitting power, can be installed in a variety of metal and non-metal containers. No harm to human body and environment.
The measurement blind area is smaller, and the canister measurement has better effect.
Shorter wavelength, more suitable for the measurement of small particulate materials.
Advanced microprocessors and unique EchoDiscovery echo processing technology are used to make the radar position meter suitable for all kinds of complex operating conditions.
Used widely used in petroleum, chemical, steel, food, coal, electricity, cement and water treatment industries, such as: large solid bin level measurement, all kinds of chemical medium level measurement, tank liquid level measurement in wastewater treatment, powder grinding equipment into the material mouth material level measurement, the material level height of the pulverized coal storehouse, lime storage of material level measurement, etc.
Technical parameter no. : SHRD21
Working mode: pulse type
Features: a variety of patented antennas, anti - condensation, crystallization, hanging material, dust, beam concentration.
Should be used: normal temperature, pressure storage containers, process containers and other occasions
Measuring range: 30m
Working frequency: 26GHz
Measurement accuracy: ± 10 mm
Display resolution: 1mm
Process temperature (- 40 ~ 80 ℃); (to 40 ~ 120 ℃; (60 ~ 250 ℃
Process pressure: normal pressure; (-0.1 ~ 4) MPa
Signal output :(4 ~ 20) mA/HART
Current resolution: 1.6uA
Power source: two-wire system (DC24V); Four-wire system (DC24V/AC220V)
Power consumption: Max.22.5mA/ Max.1VA 1W
Field display: LCD, optional
Blind area: antenna end
Fault signal: current output unchanged; 20.5 mA; 22 ma; 3.9 mA
Load resistance: Max. 500 Ω
Antenna material :(1) horn antenna/stainless steel 316L/PTFE oscillator; (2) horn antenna/stainless steel 316L/PTFE oscillator /PTFE
Mask. (3) parabolic antenna/stainless steel 316L/PTFE oscillator
Antenna structure :(1) sharp cone-shaped oscillator; (2) vertebral surface vibrator, anti-condensation; (3) parabolic antenna, 4° Open Angle
Cable parameters: cable inlet/plug 1 M20*1.5 cable inlet (cable diameter 5... 9mm), a blind plug M20*1.5
Protection grade: IP67
Relative humidity: 95%
Weight: 2 kg
Outer shell: single cavity: aluminum alloy/stainless steel 316L/PTFE/ anti-static PP; Double cavity: aluminum alloy/stainless steel 316L
Sealing ring: silicone rubber
Case window: polycarbonate
Ground terminal: stainless steel
Vibration resistance: mechanical vibration 10m/s2, (10-150) Hz
Process connection: thread G112A/ thread 112NPT/ flange/universal joint flange
Flange selection :(PTFE/PP) flange, stainless steel flange, stainless steel universal joint flange
LVFW011 temperature and pressure compensation vortex flowmeter
Features: the meter body is integrated with voltage regulation compensation function, which can measure the standard volume flow or the standard mass flow of the fluid
Can long-distance transmission of traffic signals, and computer networking, centralized management
Fully intelligent, digital circuit design, can automatically compensate the measured flow density or standard volume
The output signal is proportional to the flow, without zero drift, high precision
No moving parts inside the sensor, simple and firm structure, stable performance, long service life
Reasonable design and layout of the sensor, less pressure loss, less maintenance
The measuring range is wide and can reach 15:1 or 20:1
Flange connection or plug - in connection, easy installation and easy operation
Strong commonality
Application can be used to measure saturated steam, superheated steam, various gases (such as gas, natural gas, compressed air, oxygen, nitrogen, argon, hydrogen, carbon dioxide, etc.), water and low viscosity, low temperature liquid (such as salt water, liquid nitrogen). Gas liquid general, no need to calibrate, can accurately measure the closed pipe steam, gas and liquid flow. It is widely used in metallurgy, electric power, chemical industry, pharmacy, papermaking, food, boiler, oil pipeline and other industries.
Technical parameter: LVFW011
Should be used: gas, liquid, saturated steam, superheated steam
Flow rate range: liquid 0.5-5m/s, gas 4-70m/s
Accuracy grade: 0.2 /0.5
Range ratio: 10:1; Can be customized according to customer needs
Medium temperature: - 40 ℃ to 350 ℃
Pressure class: -0.1MPa-6.4MPa
Nominal diameter: DN25-DN1000
Signal output: 4-20ma /RS485
24 VDC power supply:
Load resistance: MAX. 500 Ω
Pressure loss: resistance coefficient CD 2.4
Power consumption: low power consumption
Field display: LCD
Protection grade: IP67
Relative humidity: 95%
Outer shell: aluminum alloy, stainless steel 316L, stainless steel 304
Process connection: flange connection
LES10 split type electromagnetic flowmeter
Functional features: the measuring channel is a section of smooth straight pipe, will not block, applicable to the measurement of solid particles containing liquid-solid two-phase fluid, such as pulp, mud, sewage, etc.;
The measured volume flow is not affected by the fluid density, viscosity, temperature, pressure and conductivity.
Different combinations of ptfe or rubber lining, HC, HB, 316L, Ti and other electrode materials can meet the needs of different media.
Series nominal size DN15 ~ DN3000, sensor lining and electrode materials have a variety of choices;
Simple structure, reliable, no moving parts, long working life;
There are no moving parts, no intercepting parts, no pressure loss and fluid blockage.
Full digital processing, strong anti-interference ability, reliable measurement, high precision;
With self - examination and self - diagnosis function.
Large diameter instruments are mostly used in water supply and drainage engineering. Small and medium caliber is often used in high demand or difficult to measure occasions, such as steel industry blast furnace outlet cooling water control, papermaking industry measurement paper pulp and black liquid, chemical industry strong corrosive liquid, nonferrous metallurgy industry pulp; Small caliber and micro caliber are often used in places with hygiene requirements such as pharmaceutical industry, food industry and biochemistry.
In addition to measuring the volume flow rate of general conductive liquid, it can also be used to measure the volume flow rate of strongly corrosive liquid such as strong acid and strong alkali and even liquid-solid two-phase suspension liquid such as mud, pulp and paper pulp. Widely used in petroleum, chemical, metallurgy, textile, paper, environmental protection, food and other industrial departments and municipal management, water conservancy construction and other fields of flow measurement.
Technical parameters
Model no. : le 10 split type electromagnetic flowmeter
Should be used: almost any conductive medium
Flow range: 0.1m/s ~ 15m/s
Accuracy grade: 1, 0.5
Range ratio: 20:1, can be customized according to customer demand
Medium conductivity: > 5us/cm
Medium temperature (20 ~ 90 ℃) - 40 ~ 100 ℃
Pressure rating: 2.5MPa or customized
Sensor diameter: DN6 ~ DN2000
Signal output :(4 ~ 20) mA/RS485
Power source: two-wire system (DC24V)
Sensor electrode materials: molybdenum stainless steel, titanium (Ti), tantalum (Ta), hastelloy (HB, HC), platinum (Pt), stainless steel coated tungsten carbide or other special electrode materials
Sensor lining materials: teflon, polyurethane, polyfluoroethylene propylene, screening PFA, polychloroprene, etc
Load resistance: MAx. 500 Ω
Power consumption: low power consumption
Field display: LCD
Protection grade: IP67
Relative humidity: 95%
Weight: 5 kg
Outer shell: aluminum alloy/stainless steel 316L
Process connection: flange connection
LES10 electromagnetic flowmeter
Functional features: the measuring channel is a section of smooth straight pipe, will not block, applicable to the measurement of solid particles containing liquid-solid two-phase fluid, such as pulp, mud, sewage, etc.;
The measured volume flow is not affected by the fluid density, viscosity, temperature, pressure and conductivity.
Different combinations of ptfe or rubber lining, HC, HB, 316L, Ti and other electrode materials can meet the needs of different media.
Series nominal size DN15 ~ DN3000, sensor lining and electrode materials have a variety of choices;
Simple structure, reliable, no moving parts, long working life;
There are no moving parts, no intercepting parts, no pressure loss and fluid blockage.
Full digital processing, strong anti-interference ability, reliable measurement, high precision;
With self - examination and self - diagnosis function.
Large diameter instruments are mostly used in water supply and drainage engineering. Small and medium caliber is often used in high demand or difficult to measure occasions, such as steel industry blast furnace outlet cooling water control, papermaking industry measurement paper pulp and black liquid, chemical industry strong corrosive liquid, nonferrous metallurgy industry pulp; Small caliber and micro caliber are often used in places with hygiene requirements such as pharmaceutical industry, food industry and biochemistry.
In addition to measuring the volume flow rate of general conductive liquid, it can also be used to measure the volume flow rate of strongly corrosive liquid such as strong acid and strong alkali and even liquid-solid two-phase suspension liquid such as mud, pulp and paper pulp. Widely used in petroleum, chemical, metallurgy, textile, paper, environmental protection, food and other industrial departments and municipal management, water conservancy construction and other fields of flow measurement.
Model no. : le 10 electromagnetic flowmeter
Should be used: almost any conductive medium
Flow range: 0.1m/s ~ 15m/s
Accuracy grade: 1, 0.5
Range ratio: 20:1, can be customized according to customer demand
Medium conductivity: > 5us/cm
Medium temperature (20 ~ 90 ℃) - 40 ~ 100 ℃
Pressure rating: 2.5MPa or customized
Sensor diameter: DN6 ~ DN2000
Signal output :(4 ~ 20) mA/RS485
Power source: two-wire system (DC24V)
Sensor electrode materials: molybdenum stainless steel, titanium (Ti), tantalum (Ta), hastelloy (HB, HC), platinum (Pt), stainless steel coated tungsten carbide or other special electrode materials
Sensor lining materials: teflon, polyurethane, polyfluoroethylene propylene, screening PFA, polychloroprene, etc
Load resistance: MAx. 500 Ω
Power consumption: low power consumption
Field display: LCD
Protection grade: IP67
Relative humidity: 95%
Weight: 5 kg
Outer shell: aluminum alloy/stainless steel 316L
Process connection: flange connection
FLD10 on - line dust detector
Measuring principle: when the dust particles in the air through the sensor, the dust scattering laser scattering to the photodiode, photodiode dust concentration of weak optical signals into a weak electrical signals, and then to electrical signal amplification, detection and a series of digital signal processing, the processing unit according to dust concentration, at the same time the output and the dust concentration corresponding to the current signal, and according to the dust concentration power output signal.
To adapt to the environment
It is applicable to the determination of dust concentration in the production site of labor department of industrial and mining enterprises
Municipal prison smoke
Scientific research, filter material performance test and other field tests
On-site dust concentration measurement, exhaust dust concentration monitoring
Management of manufacturing processes for factories requiring clean air, precision instruments, test instruments, electronic components, food, medicine, etc
Dust detection at construction or blasting sites; Site exposure monitoring
Industrial site where coal dust exists
Technical parameters
Power supply voltage: dc24v;
Communication mode: current signal 4-20ma;
RS485
Measuring range: 0-500mg /m3 (total dust)
Detection sensitivity: 1mg/m3
Measurement accuracy: 5%
Alarm signal output: the alarm value can be set arbitrarily within the range, and the high and low level alarm signal can be output
Power: 2 w or less
Weight: 6.5 Kg
Protection level: IP65

Back to Exhibitor List

IE expo China 2017 is presented by IFAT © 2017 版权所有 沪ICP备12049585号